The 801PC 3oTec detector is a combined optical, carbon monoxide and heat detector for use with MX Technology® controllers. The 801PC can be used in combination with other MX Technology® detectors with a maximum total of 250 detectors connected to a single 2 wire MXDigital loop.
Features:
Combined optical, heat and carbon monoxide detector
LPCB and VdS approved fire detector (pending)
EN50291 CO toxic gas detector
Operate simultaneously as a fire detector and CO toxic gas detector
Early detection of all fire types from slow smouldering to fast flaming
Minerva® Expert algorithms use all three elements for positive false alarm free fire detection
Optical, CO and Heat can operate independently for sequential alarm systems and CO toxic gas alert
All 3 elements are independently monitored for faults
Universal mode for maximum protection
Resilient mode for false alarm free operation in challenging environments
Use with standard or loop powered sounder base for reduced installation costs
MXDigital signalling suitable for most cable types including retro-fit
801PC 3oTec Operating Modes:
Universal Mode - EN54 pt.7 - CEA4021 - IS07240.7
Resilient Mode - EN54 pt.7 - CEA4021- IS07240.7
High Performance Optical - EN54 pt.7 - IS07240.7
Compensated CO Fire Sensing - LPS1265 - IS07240.6
Heat Detection - EN54 pt.5 A1R - IS07240.5
CO Toxic Gas Detection- EN50291
Heat Sensing Element:
High quality thermistor with very low thermal mass for added responsiveness
Optical Chamber:
The optical chamber has many advanced features that improve performance and reliability.
High intensity, short pulse width infrared light source for heightened responsiveness.
Optical feedback will verify the total optical path on every poll of the detector.
Precision optics eliminate nuisance from small insects such as thrips, without the need for a filter.
Carbon Monoxide Cell:
High efficiency electro-chemical CO detection cell
Cell integrity is continuously monitored
Increased cell capacity for durability
Cell electronically calibrated for IS07240.6 fire applications or EN50291 toxic gas applications
Associated Documents: Click on the document title to view the document on-screen.