Wet Chemical Systems - Restaurant Protection
Wet Chemical Restaurant Fire Fighting systems are based on many years experience in the design, supply, installation and commissioning of fire fighting systems.
The systems are ideally suited to meet the demands associated with today’s busy catering facilities An important characteristic
of grease fires is auto-ignition. Cooking grease at room temperature is not a problem. Its vapours, for example, are not easily
ignited. However, when heated to auto-ignition temperature - extinguishing the fire alone and removing the heat source may
not prevent re-ignition. Re-ignition can occur until the liquid is cooled below its auto-ignition temperature.
It is the principal requirement of fire extinguishing and the prevention of re-ignition that makes the Wet Chemical system the
ideal solution.
Wet Chemical - Extinguishing Action
The Wet Chemical Extinguishing agent is a potassium carbonate based solution which is discharged as fine droplets into a protected area. The main extinguishing action is by cooling caused by the heat of vapourisation. The fine spray discharge prevents the dangerous splash of hot grease or thermal shock damage to cooking appliances.
Re-ignition is prevented by saponification, a process in which the wet chemical agent combines with the grease to form a soapy layer at the surface of grease to seal off the fuel from the
oxygen, allowing the grease to cool to below it’s auto-ignition
temperature.
Installation
The Installation of fixed fire fighting equipment in busy catering
facilities requires extensive experience in the scheduling and
performance of this type of work. Our experience in the
installation of restaurant fire fighting systems ensures a
minimum of disruption. Pipework for Wet Chemical systems
may be black, chrome plated or stainless steel to suit the
particular requirements of the application.
Application
The system operates at a nominal pressure of 12 bar (175p.s.i.)
providing a fine spray discharge lasting for a nominal 45
seconds.
The unique nature of the Wet Chemical Extinguishing Agent
eliminates many of the piping limitations commonly associated
with dry chemical systems.
Clean-Up
Wet Chemical agent unlike Dry Powder may be quickly cleaned
up following a discharge resulting in shorter down time of the
cooking range.
Storage
Wet Chemical system utilise storage containers in a range of
sizes to suit the individual requirements of the hazard.
Controls
The Wet Chemical system may be controlled manually or
automatically using electrical detection equipment or
mechanical fusible link devices.
|